Explain Bernoulli’s theorem. State its application.

Bernoulli’s theorem states that the ‘total energy of a liquid flowing from one point to another remains constant’. It is applicable for non-compressible liquids. For different types of liquid flow Bernoulli’s equation changes. There is direct proportion between speed of fluid and its dynamic pressure and its kinetic energy. It can be used in various real life situations like measuring pressure on aircraft wing and calibrating the airspeed indicator. It can also be used to low pressure in the venturi tubes present in carburetor.

 Why is the orifice tab provided?

Following reasons justify for providing orifice tab:
1. Indication of orifice plate in a line
2. The orifice diameter is marked on it.
3. The material of the orifice plate.
4. The tag number of the orifice plate.
5. To mark the inlet of an orifice.

How can a D.P. transmitter be calibrated?

D.P. transmitter can be calibrated using following steps:
1. Adjust zero of Xmtrs.
2. Perform static pressure test: Give equal pressure on both sides of transmitter. Zero should not shift either side. If the zero shifts then carry out static alignment.
3. Perform vacuum test: Apply equal vacuum to both the sides. Zero should not shift.
4. Calibration procedure: Give 20 psi air supply to the transmitter and vent L.P. side to atmosphere. Connect output of the instrument to the standard test gauge. Adjust zero. Apply required pressure to the high pressure side and adjust the span. Adjust zero gain if necessary.

How is flow measured in square root?

Flow varies directly as the square root of pressure. Thus, F=K of square root of applied pressure. Since this flow varies as the square root of differential pressure. The pressure pen does not directly indicate flow. Thus flow can be determined by taking the square root of the pen. Assume the pen reads 50% of the chart. So, flow can be calculated using the pen measure in the chart.

Name different parts of a pressure gauge. Explain the use of hair spring in the pressure gauge.

Pressure gauge includes following components:
a. ‘C’ type bourdon tube.
b. Connecting link
c. Sector gear
d. Pinion Gear
e. Hair spring
f. Pointer
g. Dial
Use of hair spring: Hair spring is responsible for controlling torque. It is also used to eliminate any play into linkages.

How is automatic reference junction compensation carried out in temperature recorders?

In automatic reference junction compensation, variable nickel resistor is used. As the temperature changes, so does its resistance. This reference junction compensator is located, so that it will be at the temperature of the reference junction. The reference junction is at the poset where the dissimilar wire of the thermocouple is rejoined. This joint is invariably at the terminal strip of the instrument.

What are de-saturators?

When, in some processes, e.g. batch processes, long transient responses are expected during which a sustained deviation is present the controller integral action continuously drives the output to a minimum or maximum value. This phenomenon is called ‘integral saturation of the control unit’. When this condition is met, then this unit is de-saturated.

Explain the working of Rota meter.

Variable area meters are special form of head meters. Where in the area of flow restrictor is varied. So as to hold the differential pressure constant. The rota meter consists of a vertical tapered tube through which the metered fluid flows in upward direction. As the flow varies the ‘float’ rises or falls to vary the area of the passages that the differential across it balances the gravitational force on the ‘float’. The differential pressure is maintained constant. The position of the ‘float’ is the measure of the rate of flow.

What is the working principle of the magnetic meter?

An electric potential is developed when a conductor is moved across the magnetic field. In most electrical machinery the conductor is a wire. The principle is equally applicable to a moving, electrically conductive liquid. The primary device of commercial magnetic meters consist of straight cylindrical electrically insulated tube with a pair of electrodes nearly flush with the tube walls and located at opposite end of a tube diameter. This device is limited to electrically conducting liquids. The magnetic meter is particularly suited to measurement of slurries and dirty fluids.